Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Machine Expert, need information about User Data Type limitations. Arrays and structures complexity and size.

Issue:

Need to know the limitations for Arrays and Structures complexity and size in EcoStruxure Machine Expert.

Product:

EcoStruxure Machine Expert software (all versions).

Answer:

EcoStruxure Machine Expert/Codesys does not limit the max array size or structure complexity.

The only limitation is the memory size of the controller.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings