Scadapack Workbench will not launch

If SCADAPack Workbench will not Launch, a potential solution is

  • Open Event Viewer
  • Go to Event Viewer>Windows Logs>Application
  • Determine the Error, see example below

SW_Crash1
SW_Crash2

For SCADAPack Workbench CAM3:

  • To Correct the issue, Open the Scadapack Workbench CD installation
  • Go to the "\Prerequisites\VS2013 IsoShell" folder from the installation media
  • Install the following application manually vs_isoshell and VS12-KB3107629
  • After installing the applications manually restart your machine.

For SCADAPack Workbench CAM5:

  • To Correct the issue, under the installer folder, Open the Workbench folder
  • Go to the "\Prerequisites\VS2013 IsoShell" folder from the installation media
  • Install the following applications manually vs_isoshell and VS12-KB3107629
  • After installing the applications manually restart your machine.

If this does not help, please get in touch with your local support team for more help.

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center