What is the tightening torque settings for the earth bolts in the Acti 9 distribution boards?
The main earth bolt (provided as a kit, using M8 hardware) should be tightened to 8.0Nm, this value is printed on the auto-bag.
The main earth terminal situated at the up of the board and using an M7 x 15 combi head screw should be tightened to 3.5Nm.
The main earth terminal situated at the up of the board and using an M7 x 15 combi head screw should be tightened to 3.5Nm.
Released for: Schneider Electric UK


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.