Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to Safely Distribute Database Folders to Another Disk/Location in Geo SCADA/ClearSCADA.
⚠️*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system.
Always backup the registry before making any changes.*


In some cases, you may need to distribute Geo SCADA database folders (such as Config, Data, History, etc.) to different disks or locations for performance optimization or storage management. This can be achieved using the Registry Editor method. Below is a step-by-step guide.

Steps to Move Database Folders

Step 1: Shut Down the Geo SCADA Server

  • Right-click the Geo SCADA Server icon in the system tray.
  • Select Shutdown Server.


server shut down

Step 2: Locate the Original Database Folder

  • Navigate to the default database path:
    C:\ProgramData\Schneider Electric\ClearSCADA\Database
    Here you will find folders such as:
  • Config
  • ConfigChanges
  • Data
  • DataFiles
  • HisFiles
  • History
  • Journal
locate folder

Step 3: Move the Desired Folder

  • Copy or move the folder you want to relocate (e.g., ConfigChanges, History) to the new disk or location.

Step 4: Update the Registry

  • Open Registry Editor (regedit).
  • Navigate to:
    HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ClearSCADA\DB
  • Locate the registry key corresponding to the folder you moved (e.g., ConfigChangePath, HistoryPath).
  • Update the Value data to the new folder path.

regitry

Step 5: Restart Geo SCADA Server

  • Start the Geo SCADA server again.
  • Verify the new folder location in Server Configuration → System configuration → Location.

server config

Best Practices

  • Ensure the new location has sufficient disk space and proper permissions.
  • Avoid moving folders while the server is running.
  • Keep a backup of the original database before making changes.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings