How can we help you today?

How to save multiple variable values in Event Logging to a Single CSV File?

Issue:

Want to save data to USB drive on HMIGTO3410 by following the instruction "Save Variable to a Single CSV File, section 13.1.1.5 in the manual"

Product Line:

Vijeo Designer (all versions)

Resolution:

The following video on How to log data using Event Handling in Vijeo Designer, shows how it can be done:

https://www.youtube.com/watch?v=AvucNI5wELE

In it, they indicate to use 2 Text Resources in order to write the data on 2 lines in the file.

But, in Vijeo Designer, it is possible to use only 1 Text Resources and configure 2 (or more) messages:

Text ressource

Then when configuring the Action that will generate the messages, use only 1 Text Resource but use the 2 messages in the actions instead of 2 Text Resources and only 1 message in each.

Actions configuration

This way would be better suited for the management of messages and what they are used for in the project.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center