Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Missing the +10v supply on a ATV630/ATV930 drive

Issue:

Missing the +10v supply on a ATV630/ATV930 drive

Product Line:

ATV630/ATV930

Environment:

Missing +10v supply

Cause:

n/a

Resolution:

Would suggest to check the incoming power at L1, L2 and L3.

Then check the DC bus at PA/+ to PC/-.

If these are both ok, then measure between 24v and 0v for 24v.

Then measure between +10v to com and if all the supplies are ok, except the +10v, then appears the Main Control Board is inoperative.

Note: The Main Control Board would need to be replaced by Schneider-Electric Field Services

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings