How do I update the firmware of my SRTG 15 & 20kVA UPS?

Issue:

SRTG 15 & 20kVA UPS requires a firmware update.

Product Line:

Smart-UPS models SRTG15KXLI and SRTG20KXLI

Environment:

  • Computer with Windows 7 or Windows 10 operating system
  • The USB A to USB B type communication cable supplied with the UPS
  • "UPS-UpdateToolInstaller.zip" file - available at the end of this document
  • "15-20k V1.19 20220909.zip" Firmware File - available at the end of this document


Resolution:

NOTE: The UPS system is expected to power down during the firmware upgrade. It is recommended to turn off the load connected to the UPS before starting the firmware upgrade.

Preparation:

  1. Connect the USB A to USB B type communication cable supplied with the UPS cable between the UPS and computer.
    • 1
  2. Download the "UPS-UpdateToolInstaller.zip" and "15-20k V1.19 20220909.zip" files attached at the end of this document.
  3. Extract the "UPS-UpdateToolInstaller.zip" file.


Installing the Update Tool:

Double click the "UPS-UpdateToolInstaller.exe" file to start installing the update tool.

  1. Select OK.
    • 2
  2. Select Next.
    • 3
  3. Select Install.
    • 4
  4. Ensure that the "Launch UPS-UpdateTool" option is selected, and then select Finish. This will launch the update tool.
    • 5


Updating the UPS Firmware:

  1. Select the language: English.
    • 6
  2. Select the appropriate port number where the USB cable is connected to the computer.
    • 7
  3. Press "select" and browse to the location where the "15-20k V1.19 20220909.zip" file was downloaded in Preparation Step 2.
    • 8
    • 9
  4. Ensure both check boxes are ticked:
    • 10
  5. Select Updating:
    • 11
  6. The update may take 15-20 minutes. Once the update is completed, the update tool can be closed:
    • 12

Verifying the firmware version

Use the UPS front panel to navigate to the following menus.

  1. Press the OK key to enter the Main Menu, press the ▼ key to select Configuration and press the OK key to enter the submenu.
    • 13
  2. Press the ▼ key to select Display, and click OK to enter the submenu.
    • 14
  3. Press the ▼ key to select the Menu Type, and click OK to enter the menu type selection screen.
    • 15
  4. Press ▼ key to select Advanced, and press OK to confirm.
    • 16
  5. Press ESC key until you return to the Main Menu.
  6. In the Main Menu, press the ▼ key to select About, click OK to enter the submenu.
    • 17
  7. Select UPS and click OK to enter the submenu.
    • ​​​​​​​18
  8. Press the ▼ key to view firmware component versions.
    • ​​​​​​​​​​​​​​19 ​​​​​​​

Schneider Electric UK

Attachment(s)
UPS-UpdateToolInstaller.zip [10.77 MB]
15-20k V1.19 20220909.zip [301.17 KB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings