How can we help you today?

Are accessories from the VLS and Vario range cross-compatible?

No, they're not.

We do not have coordination between these two product lines. These products are mechanically very different design and are therefore not cross-compatible.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.