My Smart UPS Modular Ultra has a battery module error right after installation

Issue:
One of the battery modules has an error after installation
Error example: C2A1

Product Line:
Smart UPS Modular Ultra

Cause
This error happens when there a multiple battery modules on different firmware's

Resolution:
Please verify what firmware your battery module is running by going into the About->UPS->Battery (Modules) menu on the display or NMC.  If the battery with an error is running firmware 0.8.37, please let the system upgrade the battery module firmware.  In order to upgrade, leave the battery module installed.  The UPS will automatically upgrade the battery module to the latest firmware (0.8.44) after about 1 hour.  Once the battery module firmware has been upgraded, the error should clear.  If the module is already running firmware 0.8.44 or the error does not clear after update to 0.8.44, please call technical support to get it replaced.

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center