How can we help you today?

Upgrading Data Center Expert from 8.0 to 8.1 or 8.1.1 breaks EcoStruxure Building Operation integration

Issue:
Upgrading Data Center Expert from 8.0 to 8.1 or 8.1.1 breaks EcoStruxure Building Operation integration

Product Line:
EcoStruXure Data Center Expert

Environment:
DCE version 8.1 and 8.1.1
EBO potentially any version.

Cause:
If EBO integration worked on 8.0 but fails on 8.1 and 8.1.1, it is likely due to a change in authentication in DCE.
An authentication feature added to 8.1.x enabled digest authentication. While the ITA integration works fine, EBO appears to no longer be able to authinticate with DCE properly and may have the following error:
"Digest authentication failed. EWS-Server doesn't support digest. Access_Denied: 401"

Resolution:
This can not be changed in the DCE UI and will be addressed in DCE version 8.2.
Until 8.2 is released, it is suggested that you redeploy at DCE 8.0 and wait for the 8.2 release due out later this year (2024).

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center