How to Achieve Anti-pumping on NW Circuit breakers
"In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker"
You can achieve the same process in the NSX range. This could be done using MN or MX.