How can we help you today?

How to correct the Scadapack Workbench Error 0046: Insufficient reserved memory size for temporary variables

  • Increase the memory size in the Scadapack Workbench program.
  • Under the program name in solution explorer, go to properties>Memory size, see details below.
    SW_Insufficient memory

    Run the Memshow to check how many free NVram memory you have.
  • Connect to SCADAPack using SCADAPack E configurator
  • Under Transfer menu, select Remote Command Line.
    SW_Insufficient memory2


  • Then Type command Memshow, it displays information related to system memory, see details below
    SW_Insufficient memory3

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center