Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why the Schneider PLC USB Driver used for M340 and M580 PLC can’t be seen after installation?

1.Context

In certain conditions, it could happen that the installation of the SchneiderPLCUSBDriverSuite finish without error and getting the message that the driver is well installed like on the following screenshot.

installation

installation

installation

However, the PLC USB Driver can’t be seen inside the driver manager :

driver manager

Even inside the program and features of windows :

program windows

2. How to solve

To solve this problem, please follow the step below :

  • Stop ‘NetAccess Service’ in Services manually.

Service

  • Delete C:\windows\System32\UsbConnect.exe , If you can’t delete it, rename it as other name.

System32

  • Re-install the SchneiderPLCUSBDriverSuite.exe.

3. Product

SchneiderPLCUSBDriverSuite

4. Environment

Windows 10 and above

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings