How to Resolve SSH Access Issues in PowerChute Network Shutdown After Upgrading to ESXi 7.0 Update 7.0 Update 3d to 3g & from 7.0 Update 3I till 3Q?

Issue:

After upgrading to ESXi 7.0 Update 3d, SSH access might fail with one of the following symptoms:

  • If the “AcceptEnv” option is enabled in /etc/ssh/sshd_config, SSH access might fail because the SSHD process does not start, resulting in no response when connecting to the ESXi host.

Product Line:

PowerChute Network Shutdown v5.x

Environment:

VMware vSphere ESXi 7.0.3

Solution:

Do the following steps to ensure PCNS can connect to the ESXi hosts over SSH.

  1. Log on to the ESXi host via DCUI.
  2. Execute the following command:
  3. vi /etc/ssh/sshd_config
  4. Comment out or remove the option AcceptEnv.
  5. Save and exit using the command :wq!.
  6. Restart the SSH service:
  7. /etc/init.d/SSH restart

See Broadcom support article. SSH access may fail post upgrade to ESXi 7.0 Update 3d

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center