RemoteConnect Configuration Log - Invalid Field ID
I wrote a configuration to a SCADAPack 474 while online with the controller and received the following Invalid Field errors in my Configuration Log.
This typically occurs when RemoteConnect is attempting to configure functionality that the firmware does not have. This results in some intended functionality not being applied.
Configuration Log details below:
#Rebuilding Configuration from file configuration.rtu at 13:31:37 on 16-05-2024
File Attributes: 103799 bytes, 13:31:36 16/05/2024
File is valid. Rebuilding Configuration
# 7448: Invalid field Id: 354073
# 7496: Invalid field Id: 150901
# 7558: Invalid attribute for point: 551210
Configuration Rebuild Pass
To correct this issue apply the firmware bundled with the version of RemoteConnect that you're using.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.