How can we help you today?

Would it be possible to install a TNS SPD on a TN-C-S network?

Please note that the SPDs with the A9L prefix, which are compatible with TT and TNS, are also compatible with TNS part of TN-C-S networks.

In a TN-C-S network, the neutral conductor N and the protective conductor PE are combined (PEN) up to a certain point, then separated (separation of the neutral conductor N and the protective conductor PE). The A9L SPDs for TNS are therefore compatible with this type of network on the TNS part of the TN-C-S network.

For the TNC part of the TN-C-S network, a 3P surge protector compatible with TNC is required.

TNCS network

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings