How can we help you today?

Battery Module Does Not Turn On in Smart-UPS Ultra 5-10kVA or Smart-UPS Modular Ultra

Problem: The SRYLBM battery module does not turn on in Smart-UPS Ultra 5-10kVA or Smart-UPS Modular Ultra, even after tightening the thumbscrew.

Product Line: SRYLBM

Environment: SRYLBM installed in the following UPS models: SRTL5KRM2UI, SRTL5KRM2UT, SRTL8KRM4UI, SRTL8KRM4UT, SRTL10KRM2UI, SRTL10KRM2UT, SRYLxxKxxRMXLT

Cause: The switch on the battery module does not fully engage after tightening the thumbscrew.

Resolution: Use a flat head screwdriver to tighten the thumbscrew further until the battery module turns on.

IMPORTANT: Tighten with caution as over tightening may damage the thumbscrew.

img

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings