Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can an ATV900 Frame Size 7 be installed without a DC Choke?

Issue:
Can you install an ATV900 Frame Size 7 without a DC Choke?

Product Line:
Altivar 900 series Frame Size 7

Environment:
All serial numbers for Altivar 900 Series Frame Size 7

Cause:
N/A

Resolution:

You need to add a jumper between PO and PA+ when installing the drive without a DC Choke.

PA & PO Terminals

Note:

For ATV930 products that have no DC choke, a line reactor is necessary to be installed.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings