Does the iEM3400 and iEM3500 series meters support High leg Delta wiring?
Issue
Can the iEM3400 and iEM3500 series meters be wired as high leg delta or not?
Product line
iEM3400 and iEM3500
Environment
Application requires the installation of a power meter or replacement existing meter in a high leg delta system.
Resolution
No. These meters (iEM3400 and iEM3500 Series) do not support the electrical system type for High-Leg Delta.
The electrical system types supported, per the User Guide, https://www.se.com/us/en/download/document/7EN02-0438/
3PH3W
3PH4W
1PH2W L-N
1PH2W L-L
1PH3W L-L-N
1PH4W Multi L-N
As an alternative, please look at the PM5000 series for High Leg Delta supported models. See FAQ FA232893