How to configure Syslog on Control Expert?
In this FAQ, We will explain how to configure Control Expert in order to generate some syslog messages to a syslog server.
1.Security Editor configuration
First of all, before we need to configure a “profile” inside Security Editor by following the step below:
Then, in “Policies” you need to configure as followed:
2. Control Expert configuration
In project setting of Control Expert, Go to PLC Diagnostics and enable Event Logging and set the IP address and port number used for the syslog server
3. Status
When the syslog server is not present, we got the following in status bar on Control Expert:
Syslog is in Red
When the syslog server is present, we got the following in status bar on Control Expert:
Syslog is in Green
4. Syslog Server
For test purpose, we use the kiwi syslog and here the setting to configure to make it work.
In the Kiwi syslog server setup, in Input, TCP protocol need to be enable and select the right port used : 601
5. Product line
EcoStruxure Control Expert v14.1 and above
Released for: Schneider Electric UK


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.