How can you save the ATV320 Drives program with function blocks using the Multiloader device?

Issue:

Saving the ATV320 Drives program with function blocks on the Multiloader programmer.

Product Line:

ATV320 with Multiloader device.

Environment:

All

Cause:

Getting an error message when trying to download the ATV320 program with function block using the multiloader.

Resolution:

When the ATV320 has ATVLogic running, you must stop the ATVLogic running before any multiloader transfer (you must set fbCd=STOP via keypad using ATV320 integrated Jog dial). Otherwise, the transfer will not be done.

Menus

-Config

-Full

-Function blocks

-FB command (fbCd)

set to Stop.

Now you can download the ATV320 program into the Multiloader.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings