How can we help you today?

What is the default IP address of the TM5 Ethernet/IP interface module?

Issue:

Default IP address of the TM5 Ethernet/IP interface module

Product Line:

TM5NEIP1


Resolution:

The default IP address of an TM5 Ethernet/IP interface module is determined by converting the last 2 octets in the MAC address. The first 2 octets of the default IP address is fixed at 10.10. x.y , where x.y  is the last two octets of the MAC address

Example:  If the MAC address is 00.80.F4.02.EA.6A then the IP address will be 10.10.234.106

EA Hex = 234 Decimal
6A Hex = 106 Decimal

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings