How to retrieve Log Files from the CRD Head Module

1. Open EAE Buildtime and load the EAE Solution currently running on your controller.

2. Navigate to the Deploy & Diagnostics tab.

3. Log in to the device controlling the CRD head module.

4. Stop the controller by going to Action > Device actions > Stop from the Deploy & Diagnostics tab.

5. Go to the System tab, then Physical Devices, and click Start Monitoring.

1

6. Right-click on the CRD and select Fetch logs.

2

A pop-up message will confirm that the fetch was successful and display the file name and location.

3

7. Open File Explorer and navigate to the directory specified in the message. For EAE 24.1, the default location is:
C:\ProgramData\Schneider Electric\EcoStruxure Automation Expert 24.1\StudioLog

8. Send the file to Technical Support for analysis.

NOTE: