PME - Offline Device Driver Enabled devices take a long time to load registers
Issue
When trying to link a register for an ION source with its offline device driver enabled, it takes a long time to load the register list.
Product Line
Power Monitoring Expert 7.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Vista
Designer
Cause
If there are a lot of sources with their offline device driver enabled, it can reduce the performance of the offline driver software component, causing the longer load times.
Resolution
Disable the offline device driver for all but a few devices at a time. Any links to registers on offline devices created using Vista/Designer will be preserved, whether the offline device driver is enabled or disabled.
You can disable on multiple devices by following these steps:
1. Open Management Console > Devices
2. Select a source that has its offline device driver enabled. Hold the Shift key and select another device in the list to highlight multiple. Alternatively, you can press CTRL+A on your keyboard to select all devices.
3. Right-click on any of the highlighted sources > Configure Device
4. Right-click the blank space below the settings > Advanced Properties
5. Set Offline Device Driver Enabled = No
6. Click OK to save, then edit one of the devices you need to link as an offline device and re-enable the Offline Device Driver for it
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.