How can we help you today?

DCE 8.x restoring a config backup to a new server with a different mac address causes mac address error

Issue:
DCE 8.x restoring a config backup to a new server with a different mac address causes mac address error

Product Line:
EcoStruXure Data Center Expert

Environment:
DCE 8.x
Configuration backup only

Cause:
DCE sees a config backup incorrectly and when logging into the console using the "apcsetup" user, you can see the mac address error.

Resolution:
It is best to either redeploy DCE with the same mac address or if this is not possible, to create a full or sync backup and restore to the new server using that backup.

This issue is resolved in DCE 9.0

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings