Operation Modes of PowerLogic A3 Arc Flash Protection Relay

Article available in these languages: Spanish

Issue:
What are the different operation modes of PowerLogic A3 and when should each be used?

Product:
PowerLogic A3 Arc Flash Protection Relay

Model A3F6P

Model A3F12P

Model A3S6P

Model A3S12P

Environment:
Medium- and low-voltage switchgear installations requiring arc flash protection.

Cause:
Users need to understand the flexibility of PowerLogic A3 for various system architectures and selectivity requirements.

Resolution:
PowerLogic A3 supports three operation modes:

  1. Stand-alone Mode
    • Used for simple systems with a single A3F device (full size with power supply).
    • Provides independent protection using light-only criteria.
    • Example: A3F6P or A3F12P installed in incomer or feeder cubicle.
  2. System Mode
    • Up to 5 A3 devices connected via ArcEM cables.
    • Allows sharing of sensor data and commands across devices.
    • Supports selective and non-selective schemes for multi-bay systems.
    • Limitations: Total cable length ≤ 100 m; max distance between devices = 30 m.
  3. I/O Peripheral Mode
    • Integrates with V321 central unit for advanced arc protection.
    • Up to 16 A3 devices can be cascaded.
    • Enables complex schemes with current confirmation and IEC 61850/Modbus communication.

Key Considerations:

  • Use stand-alone mode for single cubicle protection.
  • Use system mode for small switchgear with multiple feeders.
  • Use I/O peripheral mode for large installations requiring SCADA integration and advanced logic.

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings