How can we help you today?

Can't configure IEC61850 in P30

Issue

Recently we received some BFO cases where customer don’t know how to configure IEC61850 in P30 relay.

11

_____________________________________________________________

Product Line

P30

_____________________________________________________________

Environment

All firmware

_____________________________________________________________

Phenomenon

MCL 61850 and CID 61850 Folder are grey color and can’t be configured.

_____________________________________________________________

Root Cause

It is needed to enable IEC61850 ed1 or ed2 first and refresh the connection.

_____________________________________________________________

Solution

Enable IEC61850 ed1 or ed2 first.

1

Then refresh the connection.

2

Then we will see MCL61850(ed1) or CID61850(ed2) folder is ready for configuration.

3

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.