Overload Characteristics for Smart-UPS On-Line Models

Issue:

What are the overload characteristic of Smart-UPS On-Line SRT and SRTL models?

Product Line:

Single-phase Smart-UPS On-Line Line SRT and SRTL models

Environment:

All serial numbers

Resolution:

Smart-UPS On-Line SRT and SRTL UPS models support the following overload conditions:

Overload CapabilityDuration
105%No limit
125%1 minute
150%30 seconds
>175%500 milliseconds