How can we help you today?

How to solve the error message "There is an incorrect username or password…" when downlaoding to a HMISCU?

Issue

When trying to download the Vijeo Designer portion to the HMISCU from Machine Expert, the following error is displayed:

"There is an incorrect username or password in the target property's download configuration. Please verify the information and try again."

Error message

Product Line

HMISCU targets

Environment

Machine Expert v2.3 with Vijeo Designer embedded v6.3.2.16 and newer

Cause

On recent Machine Expert with Vijeo Designer embedded versions, User Rights (security) has been implemented to the HMISCU targets. The username and password information must also be added on the Vijeo Designer side to download to the target.

Resolution

When using User Rights (security) on the HMISCU, the username and password must also be added on the Vijeo Designer side.

In Vijeo Designer:

-Click on the target HMISCU

-On the Property Inspector, expand Download

-User Management is Enabled by default

-Click on the 3 dots next to User Management

-Add the HMISCU security information

Picture for reference:

User Management setting

Another option is to disable the User Rights on the HMISCU, this way the username and password will not be required.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center