How can we help you today?
How do I setup Modbus serial communication between two Ecostruxure Machine Expert controllers using the Read_Var function block?
Issue:
How to setup Modbus serial communication between two Ecostruxure Machine Expert controllers using the Read_Var function block
Product Line:
Ecostruxure Machine Expert
Resolution:
In this example, the M251 is setup a Modbus Slave and the M262 as Master. Ensure that both devices serial line settings are identical
Below is the logic where the blink function is used to execute the read every second. The address table variable of the ADDM block must be used as the address(Addr pin) of the READ_VAR block. Attached is the sample project created in Ecostruxure Machine Expert V2.3
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.