How can we help you today?
Why Can I Connect to the Modicon Edge I/O NTS but Cannot Download a Configuration?
This behavior is typically caused by a version compatibility mismatch between the Modicon Edge I/O firmware and the Edge I/O Configurator version being used.
In Control Expert v16.2, the integrated Edge I/O Configurator is based on an older version. As a result, if the Network Interface Module (NIM) firmware has been upgraded to a newer revision, you may still be able to:
- Connect to the Edge I/O system
- View and monitor device status
- Access diagnostic information
However, downloading a new configuration to the NIM is not supported because the older configurator version does not fully support the newer firmware.
This limitation has been highlighted in the Modicon Edge I/O NTS Modicon Edge I/O Configurator Release Notes, page 19.
Released for: Schneider Electric UK
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.