How can we help you today?
My Smart UPS Modular Ultra UPS runtime did not update immediately when inserting a new Battery Module (BM)
Issue:
Smart UPS Modular Ultra runtime does not update when inserting a new Battery Module (BM) into the system
Product Line:
Smart UPS Modular Ultra
Resolution:
No Action is required.
The battery module will be at a different voltage than the batteries installed in the system (battery bus). The battery module will not connect (close its discharge FET) to the battery bus if the battery module voltage is higher than the battery bus voltage. This can happen if the system is on battery or if the system is online recharging previously discharged batteries. When connected to AC, the system will eventually charge the battery bus to the level of the new battery module. At that point, the new battery module will connect, and the runtime will update accordingly.
Note: It may take up to 24 hours for the batteries to charge.
Released for: Schneider Electric UK
Explore more
Product:
Range:
Explore more
Product:
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.