How can we help you today?

How to configure the History Trend to display archived values

Question

Why are archived values not displayed in the History Trend?

Answer

If archived values are not displayed in the History Trend, verify that the HMI History Trend configuration has been created and that the correct Configuration Name is used in the CAT LogData.

Follow these steps:

  1. In your project, go to Program_Archive > Configuration > HMI History Trend, right-click on HMI History Trend, and select Open.

Open_HMI,History trend

  1. In the HMI History Trend window, click Add Item and configure the popup according to the screenshot below.

History Trend config

  1. Copy the Configuration Name. In my example, the configuration name is "HistoryTrendConfigTest".

History trend name

Paste the same configuration name into the Configuration Name property of the History Trend in your CAT LogData.

History trend fp

Once this configuration is done, the issue should be resolved.

trend

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center