PowerChute Network Advanced contains a JRE version impacted by CVE-2026-114938

Issue:

PowerChute Network Advanced contains a JRE version that may be impacted by CVE-2026-114938

Product:

PowerChute Network Advanced (PCNA)

Versions: 1.0.0 and 1.0.1

Environment:

All supported Windows Operating Systems

Cause:

Vulnerability in the Oracle Java SE, Oracle GraalVM for JDK, and Oracle GraalVM Enterprise Edition products of Oracle Java SE (component: Compiler).

For more information, see: https://nvd.nist.gov/vuln/detail/cve-2026-114938

Solution:

Per https://calif.io/java4shell#poc - PCNA is not impacted, but the issue can be mitigated by adding "-XX:-UseBASE64Intrinsics" as a startup flag in PCNA.xml

To mitigate the issue:

1. Stop the PCNA service. Open a command prompt as an administrator and enter net stop pcna.
2. Edit C:\Program Files\Schneider Electric\PowerChute Network Advanced\PCNA.xml using a text editor.
3. Add "-XX:-UseBASE64Intrinsics" to the arguments list, as shown below.
<arguments>-XX:-UseBASE64Intrinsics -Dspring.profiles.active=test -Dpf4j.pluginsDir="ºSE%\plugins" -jar "ºSE%\pcna.jar"</arguments>
4. Save PCNA.xml and re-start the service net start pcna.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center