How can we help you today?

What conductor temperature rating is applicable for QMB switches?

Issue:
Conductor temperature rating for QMB switches

Product Line:
QMB panelboard, switchboard with QMB distribution.

Environment:
Products sold in North America

Resolution:
QMB switch lugs are UL listed to accept 60 or 75 degree C wires on 30 - 100 ampere switches, 75 degree C wires on 200 ampere and larger switches.