Can the conductors be brought in the rear of a low voltage dry type distribution transformer and be brought over the top of the core and coil assembly to reach the terminals? How about if they run the conductors through conduit inside the transformer?
Issue:
Transformer conductor routing
Product Line:
LV Transformers
Environment:
Applies to Ventilated and Non-Ventilated Transformers by SquareD/Schneider Electric
Cause:
The incoming conductors to the Transformer have specific entry and exit areas on the enclosure
Resolution:
SquareD/Schneider Electric Low Voltage Dry Type Distribution Transformers are front cable entry and exit unless otherwise noted on the approval drawings. The approval drawings show the only acceptable conduit entry locations for each enclosure manufactured. Under no circumstance is it acceptable to route conductors over a Transformers core and coil assembly. Approval drawings, by catalog number, are available via the Field Office.
Transformer conductor routing
Product Line:
LV Transformers
Environment:
Applies to Ventilated and Non-Ventilated Transformers by SquareD/Schneider Electric
Cause:
The incoming conductors to the Transformer have specific entry and exit areas on the enclosure
Resolution:
SquareD/Schneider Electric Low Voltage Dry Type Distribution Transformers are front cable entry and exit unless otherwise noted on the approval drawings. The approval drawings show the only acceptable conduit entry locations for each enclosure manufactured. Under no circumstance is it acceptable to route conductors over a Transformers core and coil assembly. Approval drawings, by catalog number, are available via the Field Office.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.