What is the tolerance or voltage range for Definite Purpose 8910DPA coils?
Issue:
What is the minimum and maximum control voltage range of Definite Purpose rated devices?
Product line:
NEMA Contactors and Starters
Environment:
8910 and 8911 Definite Purpose Contactors
Resolution:
Standards state that the coil must operate properly between 85 and 110 percent of the actual rated voltage or range of -15% to +10% of nominal. Hot drop out voltage is less than 60%.
What is the minimum and maximum control voltage range of Definite Purpose rated devices?
Product line:
NEMA Contactors and Starters
Environment:
8910 and 8911 Definite Purpose Contactors
Resolution:
Standards state that the coil must operate properly between 85 and 110 percent of the actual rated voltage or range of -15% to +10% of nominal. Hot drop out voltage is less than 60%.
Released for: Schneider Electric USA