**For Deletion / Duplicate of FA101827** Where can information regarding the heat contribution or heat loss of a low voltage dry type transformer be obtained?

Issue:
Transformer Heat Contribution

Product Line:
LV Transformers

Environment:
Products sold in North America

Cause:
Transformers produce different amounts of heat in operation

Resolution:
Heat contribution information can be obtained from LVGP Product Marketing/Support. If the full load losses of the Transformer are known, then the heat contribution at full load can be obtained by multiplying the loss in watts time 3.414 to yield BTU/hr. If the information is critical, it should be requested each time from Product Marketing as Transformer designs are subject to change without notice.

Example: From the typical performance data sheet, which is also obtained from Product Marketing/Support, the full load losses of an  EE30T3H is shown to be 1,303 watts. Multiplying by 3.414 yields a heat contribution at full load for the EE30T3H to be 4,448 BTU/hr.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings