How can we help you today?

Can a main lug I-Line panel be mounted as top or bottom feed?

Issue:
Incoming feed in L-Line panel

Product Line:
Panelboards

Environment:
I-Line Power Distribution Panelboards

Cause:
Mounting flexibility

Resolution:
Yes. I-Line main lug panels can be rotated in the field to accept top or bottom feed.

NOTE: Rotating the interior will affect the location of larger breakers (wide side only) on HCW / HCP, HCWM and HCWM-U / HCR-U. On a bottom feed interior, the "wide side" is on the left of the bus stack. On a top feed interior, the "wide side" is on the right side of the bus stack.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.