How can we help you today?

How do I size thermal units for an 8630 wye-delta starter?

Issue:
Selecting thermal units to protect the motor on an 8630 Wye-Delta starter

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Magnetic Contactors and Starters

Cause:
Selecting heaters to protect the motor on an 8630 Wye-Delta starter

Resolution:
You must divide the motor full load current by 1.73 and size the heaters per the appropriate chart. Check current Square D publications for thermal unit selection chart.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings