Can a transformer be flush mounted or recessed into a wall?

Issue:
Installation of transformer.

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Resolution:
A resin filled surface-mounted Transformer can be mounted to a wall. Its enclosure design maintains UL and NEC spacing from the Tansformer to the wall. A ventilated Transformer must maintain clearance indicated on its label from any vertical surface. Either can be mounted into a recess provided that the proper clearances from the walls are maintained.