What are the acceptable wire sizes for the Class 8910 Type DPA definite purpose contactors?
Issue:
Identify the wire sizes for the Class 8910 Type DPA contactors
Product Line:
8910 Definite Purpose Contactors
Environment:
NEMA Contactors and Starters
Resolution:
As listed below based on device used:
Class 8910 Type DPA12, DPA13, DPA14, DPA22 DPA23, DPA24, DPA32, DPA33, DPA34 will accept 14 awg to 8 awg solid or stranded coper wire only.
Class 8910 Type DPA42, DPA43, DPA44 will accept 14 awg to 6 awg solid or stranded coper wire only.
Class 8910 Type DPA52, DPA53, DPA62, DPA63 will accept 14 awg to 2 awg solid or stranded coper wire only.
Class 8910 Type DPA72, DPA73, DPA92, DPA93, DPA122, DPA123 will accept 14 awg to 1/0 solid or stranded coper wire only.
Class 8910 Type SYD138 & SYD230 will accept 8 awg to 350 MCM solid or stranded coper wire only.
Class 8910 Type SYD368 will accept 8 awg to 500 MCM solid or stranded coper wire only.
Identify the wire sizes for the Class 8910 Type DPA contactors
Product Line:
8910 Definite Purpose Contactors
Environment:
NEMA Contactors and Starters
Resolution:
As listed below based on device used:
Class 8910 Type DPA12, DPA13, DPA14, DPA22 DPA23, DPA24, DPA32, DPA33, DPA34 will accept 14 awg to 8 awg solid or stranded coper wire only.
Class 8910 Type DPA42, DPA43, DPA44 will accept 14 awg to 6 awg solid or stranded coper wire only.
Class 8910 Type DPA52, DPA53, DPA62, DPA63 will accept 14 awg to 2 awg solid or stranded coper wire only.
Class 8910 Type DPA72, DPA73, DPA92, DPA93, DPA122, DPA123 will accept 14 awg to 1/0 solid or stranded coper wire only.
Class 8910 Type SYD138 & SYD230 will accept 8 awg to 350 MCM solid or stranded coper wire only.
Class 8910 Type SYD368 will accept 8 awg to 500 MCM solid or stranded coper wire only.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.