Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the max size branch breaker that can be installed in an NF panel with a 400A main breaker?
Issue:
Maximum breaker for 400amp NF panel.

Product Line:
NF Panelboards

Environment:
Products sold in North America

Resolution:
The maximum branch circuit breaker is 125 amp.

One or two Powerpact J frame, 250 amp maximum, sub-feed breakers can be installed use sub-feed breaker kit NF600SFBJ and the proper back box and trim.  The NF600SFBJ requires more mounting space versus the standard enclosure.  See the Digest for sizes.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings