What is the coil burden of a 20 amp 8910DPA?
Issue:
What is the inrush and sealed VA rating of 20 amp 8910DPA?
Product Line:
Definite Purpose Contactors
Environment:
Class 8910 Types DP, DPA Contactors
Resolution:
56VA inrush and 6VA sealed for 2 & 3 pole devices , 109VA inrush and 10VA sealed for 4 pole contactors.
What is the inrush and sealed VA rating of 20 amp 8910DPA?
Product Line:
Definite Purpose Contactors
Environment:
Class 8910 Types DP, DPA Contactors
Resolution:
56VA inrush and 6VA sealed for 2 & 3 pole devices , 109VA inrush and 10VA sealed for 4 pole contactors.