Is a two step stored energy mechanism available in the PowerPact P frame breaker?

Issue:
Is a two step stored energy mechanism available in the PowerPact P frame breaker?

Product Line:
PowerPact P frame breakers

Resolution:
Yes, however they are available only as factory installed in a new breaker as the breaker block is different from a standard PowerPact P frame breaker with a toggle mechanism.
Electrically operated P-frame circuit breakers are available only in I-Line and unit mount construction up to 1200 A. These come equipped with a two-step stored energy mechanism and a spring-charging motor.  If a drawout version is required, use Masterpact NT.
Electrically operated P frame breakers contain a spring charging motor (MCH), a shunt trip (MX), and a shunt close (XF), and are available in standard or communicating versions. All 3 items (MCH, MX and XF) must be of the same voltage. An SDE overcurrent trip switch is included.