What is the terminal lug data for ALL of the 100amp Series F, US and Canada, Heavy Duty Safety Switches (for example, CH223N, CH323NDS, H223DS, H223NRB, H323NRB, H363 and H363DS etc.)?

Article available in these languages:

  • Spanish

Issue:
Product features

Product Line:
HD Safety Switch

Environment:
Product features

Cause:
Clarification

Resolution:
The Series F, 100amp Heavy Duty Safety Switchese will accept as standard (1) #12-1/0 Al or (1) #14-1/0 Cu wire per phase and neutral. The Lug conductor(or wire) temperature rating is 60 or 75 degrees C
NOTES:
1)
The only alternate lugs are compression lugs, BUT they do NOT change the wire size or quantity as mentioned above.

2) The H100XFA and H100XFA1212(which are now Obsolete and replaced with the Catalog numbers below), ONLY accepted 75 degree C copper wire and a #3 AWG copper wire was required for 100amp rating

3) The new Catalog numbers H100XBD and H100XBDAA, ONLY accept 75 degree C Copper Wire and use a #3 AWG Copper wire MAX. for 100amp rating.



Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings