Will a remote main series rated to the branch breakers installed in a main lug feed thru panelboard and to the branch breakers in the main lug panelboard that is being fed from the feed thru panelboard?
Issue:
Remote series rated to the branch breakers installed in a main lug feed thru panelboard and to the branch breakers in the main lug panelboard that is being fed from the feed thru panelboard.
Product Line:
Panelboards.
Environment:
Products sold in the United States.
Cause:
Product features.
Resolution:
Yes, providing the remote main does have a series rating to the associated branch breakers in each panelboard.
Remote series rated to the branch breakers installed in a main lug feed thru panelboard and to the branch breakers in the main lug panelboard that is being fed from the feed thru panelboard.
Product Line:
Panelboards.
Environment:
Products sold in the United States.
Cause:
Product features.
Resolution:
Yes, providing the remote main does have a series rating to the associated branch breakers in each panelboard.
Released for: Schneider Electric USA