Video: Can a Model 6 LVMCC unit be installed in a Model 5 LVMCC section?

Article available in these languages:

  • Spanish

Issue:
Can a Model 6 LVMCC unit be installed in a Model 5 LVMCC section?

Product Line:
Motor control centers

Environment:
Model 5 and Model 6 Motor control centers

Cause:
Unit compatibility and ordering

Resolution:
Yes, but there are exceptions.

The only unit (feeder or starter) that can be mounted below the top shelf is the Compact 6" unit because the 6" units do not have butterfly handles for inserting the unit.  The 12" units are larger and need the post (nib) on the midshelf to be able to insert the unit.

For Model 5 MCCs manufactured prior to May of 1992, you will require the old style midshelf part number 8045086550 when ordering a ready to assemble item from the Digest.

When placing a factory assembled order, provide the existing Model 5 LVMCC factory order number (found on the UL structure nameplate label) and the appropriate midshelf will be provided along with the unit.

The following video demonstrates Midshelf Features & Installation on Model 6 MCCs:



The following video demonstrates differences between several Model 6 MCC midshelf assemblies:

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings