How many and what size conductors will the LRD01 through LRD35 or LR3D01 through LR3D35 Tesys bimetallic overload relays accept?

Issue:
Size conductors acceptable for use with the LRD and LR3D overload relays

Product Line:
IEC Contactors and Startes

Environment:
Tesys D Overload Relays

Cause:
Identifying accepted wire sizes

Resolution:
Depends on the overload used as outlined below:

For LRD01/LR3D01 through LRD21/LR3D21 - (1) stranded copper conductor without cable end per phase = #14 AWG to #8 AWG.
For LRD01/LR3D01 through LRD21/ - (1) stranded copper conductor with cable end per phase = #16 AWG to #12 AWG.
For LRD01/LR3D01 through LRD21/ - (1) solid copper conductor without cable end per phase = #16 AWG to #10 AWG.

For LRD22/LR3D22 through LRD35/LR3D35 - (1) stranded copper conductor without cable end per phase = #14 AWG to #8 AWG.
For LRD22/LR3D22 through LRD35/LR3D35 - (1) stranded copper conductor with cable end per phase = #16 AWG to #10 AWG.
For LRD22/LR3D22 through LRD35/LR3D35 - (1) solid copper conductor without cable end per phase = #14 AWG to #8 AWG.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings