On the PowerPacT H frame breakers, where do you run the control wires for accessories?

Issue:
On the PowerPacT H frame breakers, where do you run the control wires for accessories?

Product Line:
Powerpact Molded Case Circuit Breakers

Resolution:
For unit mount circuit breakers, remove tab at the top of the cover. Route wire through wire opening in accessory cover to avoid pinching wires.

For I-line style breakers, lead wiring out to the side of the breaker behind the gap in the cover, and then behind the protective cover on the side of the breaker.

Fur further instructions, see attachment (page 3).